Solving Motor Failures Due to
High Peak Voltages and Fast Rise Times (dv/dt)
The evolution of power semiconductors has been so dramatic that today
an insulated gate bi-polar transistor (IGBT) can be turned on in just 0.
I micro-second. This results in the voltage rising from zero to peak in
only one-tenth of a microsecond. Unfortunately, there are many motors in
existence that do not have sufficient insulation to operate under these
conditions.
HIGH PEAK VOLTAGES
High peak voltages can be experienced at the motor
terminals especially when the distance between the inverter (drive) and
the motor exceeds about 15 meters. This is typically caused by the voltage
doubling phenomenon of a transmission line having unequal line and load
impedance's. Motor terminal voltage can reach twice the DC bus voltage
in long lead applications. When the characteristic load impedance is greater
than the line impedance, then voltage (and current) is reflected from the
load back toward the source (inverter). The absolute peak voltage is equal
to the sum of the incident peak voltage traveling toward the motor plus
the reflected peak voltage. If the load characteristic impedance is greater
than the characteristic line impedance, then the highest peak voltage will
be experienced at the load (motor) terminal. If the DC bus voltage is 850
volts, then motor terminal voltage could reach 1700 volts peak.
FAST VOLTAGE RISE TIMES
Fast voltage rise times of 1600 volts per microsecond
can be typical as the motor lead length exceeds just a few hundred feet.
Voltage rise time is referred to as dv/dt(change in voltage versus change
in time). When the rise time is very fast the motor insulation system becomes
stressed. Excessively high dv/dt can cause premature breakdown of standard
motor insulation. Inverter duty motors typically have more phase-to-phase
and slot insulation than standard duty motors (NEMA design B).
When motors fail due to insulation stress caused by high peak voltage
and fast voltage rise times (high dv/dt) they have common symptoms. Most
failures of these types occur in the first turn as either a phase-to-phase
short or phase to stator short. The highest voltage is seen by the first
turn of the winding and due to motor inductance and winding capacitance
of the motor, the peak voltage and dv/dt decay rapidly as the voltage travels
through the winding. Normally, the turn to turn voltage in a motor is quite
low because there are many turns in the winding. However, when the dv/dt
is very high the voltage gradient between turns and between phase windings
can be excessively high, resulting in premature breakdown of the motor
insulation system and ultimately motor failure. This problem is most prevalent
on higher system voltages (480 & 600 volts) because the peak terminal
voltage experienced often exceeds the insulation breakdown voltage rating
of the motor.
STANDARD MOTOR CAPABILITIES
Standard Motor Capabilities established by the
National Electrical Manufacturers Association (NEMA)and expressed in the
MG- I standard (part 30), indicate that standard NEMA type B motors can
withstand 1000 volts peak at a minimum rise time of 2 u-sec
(microseconds). Therefore to protect standard NEMA Design B motors, one
should limit peak voltage to 1KV and reduce the voltage rise
to less than 500 volts per micro-second.
SOLUTIONS
There are several solutions available to solve this problem, each offering
a different degree of protection at a different price.
- Inverter Duty motors should be considered
for all new IGBT drive installations. They offer increased winding slot
insulation, increased first turn insulation, and increased phase- to-phase
turn insulation. They are more expensive than standard design B motors
but are the best motor for the job when it will be controlled by an IGBT
variable frequency inverter. The NEMA Standard MG- I (part 3 1) indicates
that inverter duty motors shall be designed to withstand 1600 volts peak
and rise times of >0.1µsec. Nevertheless, it is wise to confirm the
actual motor capability with the manufacturer.
- Minimize Cable Length between the
inverter and motor. Quite often this is somewhat uncontrollable, especially
when the application is downhole pumping where the motor is required to
be a great distance from the inverter. The longer the cable, the greater
the capacitance of the cable, the lower the impedance of the cable and
thus a greater mis-match will result between the characteristic line and
load impedance's, resulting in higher peak voltage at the motor (load)
terminals. Minimize this length whenever possible to avoid problems.
- Tuned Inductor & Capacitor (LC) Filters are an effective means of taming the output voltage waveform and protecting
the motor. An "LC" circuit can result in the best voltage waveform
but at a relatively high cost and with some future considerations. Of course
these filters are "low pass shunt type filters" tuned for some
specific frequency, often in the range of 1 kHz to 2Khz. Because these
filters have essentially zero impedance at there resonant frequency, it
is very important that the inverter switching frequency not be set too
low. The threat exists that someone may vary the carrier frequency (at
a later date) without consideration for the existence of a low pass filter
resulting in damage to the inverter or filter. One should be very careful
when applying this type of filter on the output of an inverter with variable
carrier frequency. LC filters for this purpose cost approximately 3-4 times
the cost of a load reactor.
- RC Snubber Networks can reduce the
slope of the voltage waveform leading edge and reduce the peak voltage
of the waveform but they have a minimal effect on the actual waveshape.
They perform marginally when compared to the other solutions discussed
herein. At an intermediate cost, they provide a marginal benefit. The cost
of these network can be 2-3 times the cost of a load reactor.
- Load Reactors are the most cost effective means of solving high dv/dt and peak voltage problems associated
with IGBT inverters. Typical experience is that peak voltage is limited
to I 000 volts or less (actual value varies based upon system voltage).
Voltage rise time (dv/dt) is typically extended to several micro-seconds
resulting in only about 75 - 200 volts per micro- second rise times. Usually
the load reactor is all that is needed to adequately protect the motor
from dv/dt and to allow full warranty of the motor in IGBT inverter applications.
(Some motor manufacturers do not offer a warranty in IGBT applications
if a load reactor is not installed).
Whether you install the load reactor at the inverter or at the motor,
it will provide you with protection for your motor. It offers the best
dv/dt reduction when it is placed at the inverter and this is usually the
easiest place to add the reactor. Placement at the inverter also provides
voltage stress protection for the motor cables. Of course there are some
applications that may require the addition of the load reactor at the motor
terminals. This will also provide very good protection of the motor because
the IGBT protected reactor acts like the first turns of the motor. The
motor is protected well in this case, however the motor cables are not
protected from voltage stress.
GUARD-AC LINE/LOAD REACTORS
"Guard-Ac" Line/Load Reactors manufactured by MTE Corporation,
are specially constructed with IGBT protection.
They have a 4000 volt rms(5600Vpeak) insulation
dielectric strength and are approved by both CSA and UL (UL506 & UL508).
Only reactors approved to UL506 have the high dielectric strength (4000
volts) required for IGBT applications.
MTE Corporation Line/Load reactors
also feature "Triple Insulation" on the first two and
last two turns of each coil providing over 10,000 volts strength. Our standard
Line/Load Reactors are suitable for use on IGBT inverter outputs with switching
frequencies up to 20Khz.
|