Reactors Provide a Low-Cost Solution to
Inverter/Drive Power Quality
Three phase line reactors offer an economical solution to a
variety of application problems in variable-speed drive installations. Reactors
solve problems on either the input or the output of the drive if the reactor is
compensated to handle the effects of harmonics. To see where these reactors fit
in today's technology, we have to go back 25 years to the introduction of
low-voltage industrial drives. Often, the installation required a voltage
step-up or step-down and line isolation was almost universally recommended. The
isolation transformer provided both line isolation and voltage transformation.
It became standard practice to include a drive isolation transformer with
nearly every drive installation.
|
The reactor acts as a current-limiting device and filters the
waveform and attenuates electrical noise and harmonics associated with the
inverter/drive output. |
As the industry progressed, drive voltage ratings increased. Some even
developed with dual voltage ratings. Multiple power systems appeared in
industrial plants and dual voltage motors became more popular. With these and
other improvements, it became less necessary to alter the line voltage
supplying the drive. Then, the drive industry developed internal isolation and
ground fault protection systems. Thus the need for external isolation all but
disappeared. The result was a significant cost reduction for a drive system
and sales of the new electronic drives soared.
|
Line reactors protect ASD's, extending motor life, reducing power
line distortion, attenuating harmonics and eliminating nuisance tripping.
|
Soon, users of these new, economical and efficient drives began experiencing
nuisance problems not previously encountered with the older, isolation
transformer protected systems. With the isolation transformer gone, the
quality of the power delivered to the drive became more evident. The drives
were very sensitive to line fluctuations and other nuisance problems not noticed
before. A solution had to be found because the isolation transformer was too
expensive to be put back into the circuit.
The line reactor was developed as a low-cost solution to the problem. The
reactor acts as a current-limiting device and filters the waveform and
attenuates electrical noise and harmonics associated with the inverter/drive
output. In this respect, the line reactor even surpasses the isolation
transformer at a fraction of the transformer's cost. Line reactor costs are
typically just 1/5 the cost of a comparable isolation transformer.
Among the harmonic compensated line reactors benefits are:
- Virtual elimination of nuisance tripping of drives due to utility power factor correction capacitor switching
- Attenuation of line harmonics
- Extended switching component life (transistors, SCRS)
- Extended motor life
- Reduced motor operating temperature (20 to 40°C)
- Reduced audible motor noise (3 to 5 db)
- Minimized power disturbances
- Filtered electrical noise (pulsed distortion and line notching)
- Waveform improvement
Harmonic Compensation
As the name implies, line reactors are typically used on the line side of
an ASD (adjustable-speed drive), as shown in Figures 2(a) and 2(b) for single
and multiple motors. Some higher level design reactors, are harmonic
compensated and can be successfully used on the load side of the drive (between
the drive and motor) as well as the input (line) side of the circuit. Figure
3(a) shows a typical reactor on the load side of a single motor and Figure 3(b)
is the configuration for multiple motors.
Harmonic compensated line reactors are specially designed to handle the
waveform's harmonic content. This compensates for the effect of higher total
rms current as well as higher frequencies present in the waveform and may be
used effectively on either the line or load side of any ASD.
Reactors are used on the load side of an ASD as a current-limiting device to
provide protection for the drive under motor short circuit conditions. Here,
the line reactor slows the rate of rise of the short circuit current and limits
the current to a safe value. By slowing the rate of current rise the reactor
allows ample time for the drive's own protective circuits to react to the short
circuit and trip out safely. Also, the reactor absorbs surges created by the
motor load that might otherwise cause nuisance tripping of the drive. Machine
jams, load swings and other application changes to the drive load cause motor
load surges.
Looking at the load side reactor from the motor view, the ability of the
reactor to filter the waveform produced by the ASD improves motor performance
and the total system performance. Due to higher frequency pulses generated by
the drive to produce the waveform, motors typically run hotter than normal,
resulting in lower efficiency and shorter life. Unprotected motors must often
be oversized to compensate for the higher frequencies and harmonic currents that
are present in the drive output waveform. Waveform filtering by the reactor
reduces the load side harmonic content, reduces thermal current affecting the
motor and filters pulsed distortion. The reactor attempts to recreate a perfect
sine wave, thus improving motor efficiency. This extends motor bearing life,
increases horsepower output by 25-30%, and can reduce audible noise by as much
as 3-5 decibels. Tests have shown that motor temperatures can be reduced as
much as 20 to 40ºC using a harmonic-compensated reactor.
On the line side of the ASD system, reactors also serve bidirectional
functions. When the local utility switches power factor correction capacitors
onto the electrical power grid, it creates voltage spikes. The proper impedance
reactor in the input circuit virtually eliminates nuisance tripping of drives
due to these voltage spikes. Also, the reactor can protect from line sags
because it performs a line stabilizing function. Initially, this may seem
unusual because the reactor adds impedance to the circuit, which causes a
voltage drop. An important, overlooked factor is that the reactor has
significant inductance so it opposes any rapid change in current. Most voltage
sags are the result of excessive loading or current surges. Thus, by
stabilizing the current waveform, the reactor can indirectly solve both
overvoltage and undervoltage tripping problems.
Looking on the line side from the opposite direction, the reactor filters
out both pulsed and notched distortion. This minimizes interference with other
sensitive electronic equipment (other ASDS, PCs, mainframe computers, logic
controllers, telecommunications systems, monitoring equipment). The line
reactor has been proven effective in reducing harmonics emitted by the drive
onto the incoming power line.
Harmonic distortion test results shown in Figure 4 verify the effects of
harmonic current distortion on the input side of a 5HP inverter ASD.
Reactor Impedance
Line reactors are rated in percent impedance to retain some conformity with
the ratings of conventional drive isolation transformers. We can determine the
impedance rating of a conventional isolation transformer with the following
procedure:
- Short circuit the secondary winding.
- Increase the primary voltage while monitoring secondary current.
- Measure the primary voltage that causes rated secondary current to flow.
- Compare this value with the rated primary voltage to obtain a ratio equal to the transformer impedance rating.
Reactor impedance must be measured differently because the reactor is a
series, current-dependent device as opposed to the transformer that is a
parallel, voltage-dependent device. To determine percent impedance of a
single-phase reactor, measure its voltage drop with rated current flowing
through it. Compare this voltage with the line voltage for percent impedance.
You can connect two phases in series with single-phase voltage applied. Measure
the total voltage drop across both coils and compare it with the system voltage
for the impedance rating. For example, if the voltage drop across the reactor
is 12V for a 480V line, the percent impedance is 12/480 X 100, or 2.5%.
Test a three-phase reactor with all three phases energized at rated current.
With all phases energized, measure the voltage across any one phase and divide
it by the system voltage. Multiply this value by 1.73 (square root of 3) and
again by 100 for percent impedance. As an example, if the reactor drop is 8.3V
with a 480V line, the percent impedance is 8.3/480 X 1.73 X 100, or 2.99%. If
you energize only one phase of a three-phase reactor and compare the voltage
drop with the system voltage for the impedance calculation, the calculated value
indicates only 70-75% of actual value.
Line reactors are rated in percent impedance to retain some
conformity with the ratings of conventional drive isolation transformers.
It is difficult for the user to test a reactor for conformance to a
specification when reactors are rated only in percent impedance. For a more
accurate test verification, it is helpful to find the reactor's actual
inductance. This can be done in a manner similar to the impedance calculation
as follows:
First, energize all three phases of the reactor at rated current. The
measured voltage equals the current times the inductive reactance (XL, which is 2(pi) times the frequency times the inductance).
For a 60Hz system, the inductance equals the voltage divided by the current
times 6.28 (2(pi)) times 60.
Using a meter or bridge system to test line reactors usually produces false
readings for two reasons. First, this is only for single-phase testing so it
indicates a value that is 25-30 % less than actual. Second, meter or bridge
tests are at such a low current level that the reactor's core and gap remain
unenergized.
Reactors are installed in HVAC equipment, machine tools, elevators, printing
presses, UPS equipment, computer mainframes, harmonic filters, robotics
equipment, ski lifts, wind generators, electric cars, trams, and many other
types of equipment using drives or inverters. For additional information,
contact the authors at (414) 253-8200.
|