Line/Load Reactors
Detailed Product Data

HARMONIC REDUCTION Because all standard MTE reactors are compensated for harmonics (current and frequency), they are extremely effective at reducing the amount of harmonics which are produced by a drive/inverter. Use 5% impedance, harmonic compensated reactors for the best single stage reduction of harmonic distortion. For the guaranteed harmonic mitigation see MTE Matrix Filters.
Quick Links

Product Overview
Detailed Product Data
Selection Tables
Specification Table
Application Notes
Declaration of Conformity
Technical User Manuals
Product Brochure
Selection Brochure


Percent Harmonics vs Total Line Impedance
Total Input Impedance
Harmonic 3% 4% 5% 6% 7% 8% 9% 10%
5th 40 34 32 30 28 26 24 23
7th 16 13 12 11 10 9 8.3 7.5
11th 7.3 6.3 5.8 5.2 5 4.3 4.2 4
13th 4.9 4.2 3.9 3.6 3.3 3.15 3 2.8
17th 3 2.4 2.2 2.1 0.9 0.7 0.5 0.4
19th 2.2 2 0.8 0.7 0.4 0.3 0.25 0.2
%THID 44.13 37.31 34.96 32.65 30.35 28.04 25.92 24.68
TRMS 1.09 1.07 1.06 1.05 1.05 1.04 1.03 1.03
Harmonic Distortion
REACTOR LINEARITY
This curve illustrates the linearity of MTE reactors. Even at 150 percent of their current rating, these reactors still have 100% of their nominal inductance. This assures maximum filtering of distortion even in the presence of severe harmonics and best absorption of surges. The typical tolerance on rated inductance is plus-or-minus 5 percent. Reactor Linearity Curve
YOU BENEFIT FROM THESE UNIQUE FEATURES
HARMONIC COMPENSATION makes MTE reactors suitable for use on either the drive input or drive output. They are designed to carry full rated fundamental current plus handle current and frequencies associated with harmonics up to 50 percent more.

TERMINALS are provided as standard to save installation cost and minimize panel space. Finger proof (IP20) terminals are provided through 45 amps, solid copper box lugs above that to 400 amps. Tab type terminals are available as an option.

IGBT PROTECTION allows all MTE standard reactors to be used on the output of variable frequency drives including IGBT types with switching frequencies up to 20 KHZ. A premium dielectric system is utilized to protect the first, last and end turns from the potentially high circuit peak voltages and fast dv/dt which are experienced in applications with long leads between the inverter and motor. Additionally, the general dielectric system of each reactor meets UL-506 (4000 volts rms).

EPOXY IMPREGNATION minimizes audible noise in the reactor and enhances structural integrity.

HIGH SATURATION CURRENT RATING of MTE reactors maximizes their surge current protection capability. MTE reactors absorb many of the power line disturbances which cause nuisance trips on voltage source inverters.



OUTLINE DIMENSIONS
All MTE reactors are supplied with field wiring terminals, as illustrated. Units rated 45 amperes or below are supplied with the international terminal block as shown. Reactors rated above 45 amperes thru 400 amperes are supplied with solid copper box lugs. Larger reactors are supplied with copper tab type terminals. Refer to these outline drawings and the table on page 7 for reactor dimensions. Outline Dimensions
MOTOR PROTECTION
Reactors provide a level of protection from the high peak voltages and fast reise times (dv/dt) which can be exsperienced in IGBT inverter applications when the distance between the inverter and the motor is long.Refer to MTE application guides to determine if a reacdtor will offer suitable protection in your application or whether you should consider a dV/dt or sine wave filter.
For 1000 foot guaranteed protection see MTE DVDT Filters
To supply a guaranteed 5% THVD sine wave at the motor terminals see MTE sine Wave Filters.
Motor Protection
VOLTAGE SPIKE PROTECTION
A 3% impedance reactor is very effective at protecting against damage to or nuisance tripping of AC voltage source inverters, due to voltage spikes.

Voltage spikes on the AC power lines cause elevation of the DC Bus voltage which may cause the inverter to "trip-off" and indicate an over-voltage protection condition. Use reactors to absorb these line spikes and offer protection to the rectifiers and DC Bus capacitors while minimizing nuisance tripping of the inverter.
Spike Protection
NEMA 1 CABINETS
NEMA Cabinets
All MTE reactors are available as either open type or in a NEMA Type 1 general purpose enclosure. To order a reactor mounted in a cabinet simply change the second last digit of the part number from "0" to "1". Example RL- 00802 becomes RL-00812.

Reactor Part Number Type H W D WGT. (LBS) Cabinet
RL-002XX, RL-004XX, RL-008XX,
RL-012XX, RL-01801, RL-01802
Wall
Mount
8 8 6 6 CAB-8
RL-01803, RL-025XX, RL-035XX
RL-045XX, RL-055XX, RL-080XX,
RL-100XX, RL-130XX, RL-160XX, RL-200XX, RL-25001
Floor 13 13 13 18 CAB-13V
RL-25002, RL-25003, RL-320XX,
RL-400XX, RL-500X1
Floor 24 17 17 27 CAB-17V
RL-500X2,RL-500X3,RL-600XX Floor 47 27 25 144 CAB-26C
RL-750XX Floor 31 47 25 158 CAB-30B


To select the Line/Load Reactor for your application see:
Selection Tables
Specification Table


Back to top



WORLD HEADQUARTERS
an SL Power Electronics Company
N83 W13330 Leon Dr.
Menomonee Falls, WI 53052 USA

Search
Subscribe



Line/Load Reactors Harmonic Filters RFI/EMI Filters DC Link Chokes
Surge Arrestors 3rd Harmonic Filters Motor Protection Filters

Home Technical Support News & Events Company Profile Contact Us Sitemap

Copyright © MTE Corporation | All Rights Reserved Privacy Statement